Product Features
• Integrate functions such as battery data sampling, fault diagnosis, and datamanagement into one unit.
• The two-tier architecture of the BMs system supports 2 isolated CAN channels, 2isolated RS485 channels, and l Fast Ethernet communication channel.
• 3-channel voltage sampling, 4-channel temperature sampling, and the maximumvoltage at the cluster end is up to 1500 V.
• Built-in soc/sOH multi-dimensional algorithm accurately tracks the battery's actualstate.
• Support for battery (single cell, module, cluster) overvoltage, undervoltage, voltagedifference, overcurrent, undercurrent, overtem- perature, undertemperature,
shortcircuit, insulation alarms and protections.
• Supported local and online program upgrade.
Product Specifications
Operating Conditions
|
Power Supply |
Power Supply Range |
9V to 30V |
|
Rated Power Consumption |
≤2.5W |
|
|
Operating Environment |
Operating Temperature |
-20℃ to +65°C |
|
Storage Temperature |
-40℃ to +125°C |
|
|
Relative Humidity |
5% to 95% RH |
|
|
Environmental Pressure |
80kPa to 110kPa |
|
|
Altitude |
0m to 2000m |
Basic Functions
|
Voltage Sampling |
Sampling Range |
0V to 1500V |
|
Number of Sampling Channels |
3 |
|
|
Sampling Accuracy |
≤±0.5%FS(0V to 1500V full-scale range) |
|
|
Sampling Resolution |
0.1V |
|
|
Sampling Rate |
100ms |
|
|
Electrical lsolation |
5000Vdc/3536Vac |
|
|
Current Sampling |
Sampling Range |
±2000A |
|
Number of Sampling Channels |
4 (supports Hall, shunt, CAN) |
|
|
Sampling Accuracy |
± 0.5% FS |
|
|
Sampling Resolution |
0.1A |
|
|
Sampling Rate |
50ms |
|
|
Electrical lsolation |
5000Vdc/3536Vac |
Basic Functions
| Insulation Sampling | Sampling Range | 0MΩ to 10MΩ |
| Insulation Sampling | Sampling Accuracy | 10% (within 1MΩ) |
| Sampling Rate | 60s (Adjusted according to the Y-capacitance of the PCS) | |
| Electrical lsolation | 5000Vdc/3536Vac | |
| Temperature Sampling | Sampling Range | -40°C to +125°C |
| Sampling Accuracy | Accuracy s 1C if -20°C ≤T≤ +65°C | |
| Accuracy s 2℃ if -40℃ ≤T<-20°C or +65°C | ||
| Number of Sampling Channels | 4 | |
| Sampling Rate | Refresh all 4 channels every 100ms | |
| Sampling Resolution | 0.1℃ | |
| Active Output | Supports 4 channels of high-side drive output(total positive, negative pre-charge relay control) | High-side output voltage range: gvdc to 30vdc |
| Max 1.5A current output per channel | ||
| Supports 4 channels of low-side drive output(total positive, negative pre-charge relay control) | Low-side output voitage range: gvdc to 30vdc | |
| Max 1.5A current output per channel | ||
| 2 Reserved Dry Contacts | Dry Contact Specifications | 24Vdc/1A |
| Electrical lsolation | Insulation withstand voltage of contact and coil is 4000Vac | |
| 8-Channel Digital Signal Input Detection | 3-Channel High-level DI Detection | High voltage range: 17Vdc to 30vdc |
| 3-Channel Low-level Dl Detection | Low voltage range: <0.5Vdc | |
| 2-Channel lsolation | 2-channel isolated input | |
| IO Port | 2-Channel Bidirectional lO Port | Supports bidirectional blind insertion |
| Reading Level Range | 0V to 30V | |
| Controls | Input/Output | |
| RTC | Onboard clock power (Ycapacitor),storage operating time | 8 months (when fully charged) |
| Power Supply Output | 1-Channel 12V Peripheral | 9Vds to 12Vdc/6W |
| Power Supply | ||
| 1-Channel 5V Peripheral | 5Vdc/2.5W | |
| Power Supply | ||
| SOC Estimation | Accuracy | ≤5% |
Data Logging
|
Data Logging Function |
Historical Data Logging Fault Data Logging |
Storage space: 256MB |
|
Internal Parameter Storage |
Memory: 512KB |
Communication Function
|
Communication Function |
2-Channel lsolated CAN |
Communication speed: 125/250/500 KB/s available Isolation Voltage: 2500vdc |
|
2-Channel lsolated Rs485 |
Communication Speed: 9600bps Isolation Voitage: 2500vdc |
|
|
LAN Signal |
1-channel, 10/100 Mb/s |
Diagnostics
|
Diagnostics |
Module Diagnostics |
A comprehensive diagnosis function that conducts tests on components such as voltage, temperature, communication, clock, and memory after power-on to ensure the proper operation of the module |
Parameter Settings
|
Configurable Parameters |
Personalized Configuration |
Parameters can be configured using the host computer/display control interface based on customer requirements and the characteristics of the battery |
Dimensions
|
Physical Dimensions |
LxWxH |
343mm×108.5mm×32mm |
Hot Tags: battery management system bcu, China battery management system bcu manufacturers, suppliers, factory, digital energy partnership in the cloud, compact power station, energy cloud services, digital energy privacy in the cloud, cloud energy connectivity, cloud energy scalability