Battery Management System BCU

Battery Management System BCU
Details:
Product Name: Battery Management System (BMS) | BCU
Main Features:
• Integrate functions
• Supports different channels
• The maximum voltage at the cluster end is up to 1500 V
• Accurately tracks the battery's actual state
• Support for battery insulation alarms and protections
• Supported local and online program upgrade
Send Inquiry
Description
Technical Parameters
Product Features

 

• Integrate functions such as battery data sampling, fault diagnosis, and datamanagement into one unit.
• The two-tier architecture of the BMs system supports 2 isolated CAN channels, 2isolated RS485 channels, and l Fast Ethernet communication channel.
• 3-channel voltage sampling, 4-channel temperature sampling, and the maximumvoltage at the cluster end is up to 1500 V.
• Built-in soc/sOH multi-dimensional algorithm accurately tracks the battery's actualstate.
• Support for battery (single cell, module, cluster) overvoltage, undervoltage, voltagedifference, overcurrent, undercurrent, overtem- perature, undertemperature,

  shortcircuit, insulation alarms and protections.
• Supported local and online program upgrade.

 

Product Specifications

 

Operating Conditions

Power Supply

Power Supply Range

9V to 30V

Rated Power Consumption

≤2.5W

Operating Environment

Operating Temperature

-20℃ to +65°C

Storage Temperature

-40℃ to +125°C

Relative Humidity

5% to 95% RH

Environmental Pressure

80kPa to 110kPa

Altitude

0m to 2000m

 

Basic Functions

Voltage Sampling

Sampling Range

0V to 1500V

Number of Sampling Channels

3

Sampling Accuracy

≤±0.5%FS(0V to 1500V full-scale range)

Sampling Resolution

0.1V

Sampling Rate

100ms

Electrical lsolation

5000Vdc/3536Vac

Current Sampling

Sampling Range

±2000A

Number of Sampling Channels

4 (supports Hall, shunt, CAN)

Sampling Accuracy

± 0.5% FS

Sampling Resolution

0.1A

Sampling Rate

50ms

Electrical lsolation

5000Vdc/3536Vac

 

Basic Functions

Insulation Sampling Sampling Range 0MΩ to 10MΩ
Insulation Sampling Sampling Accuracy 10% (within 1MΩ)
Sampling Rate 60s (Adjusted according to the Y-capacitance of the PCS)
Electrical lsolation 5000Vdc/3536Vac
Temperature Sampling Sampling Range -40°C to +125°C
Sampling Accuracy Accuracy s 1C if -20°C ≤T≤ +65°C
Accuracy s 2℃ if -40℃ ≤T<-20°C or +65°C
Number of Sampling Channels 4
Sampling Rate Refresh all 4 channels every 100ms
Sampling Resolution 0.1℃
Active Output Supports 4 channels of high-side drive output(total positive, negative pre-charge relay control) High-side output voltage range: gvdc to 30vdc
Max 1.5A current output per channel
Supports 4 channels of low-side drive output(total positive, negative pre-charge relay control) Low-side output voitage range: gvdc to 30vdc
Max 1.5A current output per channel
2 Reserved Dry Contacts Dry Contact Specifications 24Vdc/1A
Electrical lsolation Insulation withstand voltage of contact and coil is 4000Vac
8-Channel Digital Signal Input Detection 3-Channel High-level DI Detection High voltage range: 17Vdc to 30vdc
3-Channel Low-level Dl Detection Low voltage range: <0.5Vdc
2-Channel lsolation 2-channel isolated input
IO Port 2-Channel Bidirectional lO Port Supports bidirectional blind insertion
Reading Level Range 0V to 30V
Controls Input/Output
RTC Onboard clock power (Ycapacitor),storage operating time 8 months (when fully charged)
Power Supply Output 1-Channel 12V Peripheral 9Vds to 12Vdc/6W
Power Supply
1-Channel 5V Peripheral 5Vdc/2.5W
Power Supply
SOC Estimation Accuracy ≤5%

 

Data Logging

Data Logging Function

Historical Data Logging Fault Data Logging

Storage space: 256MB

Internal Parameter Storage

Memory: 512KB

 

Communication Function

Communication Function

2-Channel lsolated CAN

Communication speed: 125/250/500 KB/s available

Isolation Voltage: 2500vdc

2-Channel lsolated Rs485

Communication Speed: 9600bps Isolation Voitage: 2500vdc

LAN Signal

1-channel, 10/100 Mb/s

 

Diagnostics

Diagnostics

Module Diagnostics

A comprehensive diagnosis function that conducts tests on components such as voltage, temperature, communication, clock, and memory after power-on to ensure the proper operation of the module

 

Parameter Settings

Configurable Parameters

Personalized Configuration

Parameters can be configured using the host computer/display control interface based on customer requirements and the characteristics of the battery

 

Dimensions

Physical Dimensions

LxWxH

343mm×108.5mm×32mm

 

 

Hot Tags: battery management system bcu, China battery management system bcu manufacturers, suppliers, factory, digital energy partnership in the cloud, compact power station, energy cloud services, digital energy privacy in the cloud, cloud energy connectivity, cloud energy scalability

Send Inquiry